This site does NOT use any profiling cookie. The only used cookie are: technical cookie.
If you want to know more about the use of cookies on the site, please read our extended information.

Pantograph (VR2D)

Products > Disconnectors

The pantograph disconnector consists of two articulated half-arms which, by moving in a coordinated way and “vertically” on the plane of the insulators, close the circuit on a fixed contact connected the upper busbar.

Pantograph disconnectors are an ideal solution for connection to busbar systems, since they allow minimizing the substation area and ensure the maintenance (disconnector arms included) of the bay inside which the equipment is installed, without putting the upper busbar out of service.

Compared to the semi-pantograph disconnector (SSP), the pantograph model provides a wider contact zone which makes it suitable for substations with busbars made up with flexible conductors.

Rated voltage: 72.5 - 550 kV

Rated continuous current: up to 6000 A

Rated short-time withstand current: up to 63 kA (3 s)

Brochure

VR2D 72.5-550 kV
Don't you see the brochure?Click here

Owing to the constant development of our products, the information included in the brochure might be not fully up-to-date.